MULTIPLE SET TEMPERATURE
With the Model 5CX-500 Temperature Controller

Select the desired temperature T1 through T5. The lowest tremperature will be T5. Adjust the thermal system with the controller set temperature and bandwidth adjustments for temperature T5.

Refer to temperature sensor resistance charts for the sensor resistance at the selected temperatures.

Select R1 through R4 such that the temperature sensor resistance at T5 minus the temperature sensor resistance at the new temperature (T1 through T4) is equal to the resistor value (R1 through R4, respectively).

Example:

(T5 sensor resistance) - (T1 sensor resistance) = R1

Use your browser's "back" button to return to the previous page.